I. Short circuit current withstand capacity
This criteria is applied to determine the minimum cross section area of the cable, so that cable can withstand the short circuit current.Failure to check the conductor size for short-circuit heating could result in permanent damage to the cable insulation and could also result into fire. In addition to the thermal stresses, the cable may also be subjected to significant mechanical stresses.
II. Continuous current carrying capacity
This
criteria is applied so that cross section of the cable can carry the
required load current continuously at the designed ambient temperature
and laying condition.
III. Starting and running voltage drops in cable
This
criteria is applied to make sure that the cross sectional area of the
cable is sufficient to keep the voltage drop (due to impedance of cable
conductor) within the specified limit so that the equipment which is
being supplied power through that cable gets at least the minimum
required voltage at its power supply input terminal during starting and
running condition both.1. Criteria-1 Short circuit capacity
The maximum temperature reached under short circuit depends on both the magnitude and duration of the short circuit current. The quantity I2t represents the energy input by a fault that acts to heat up the cable conductor. This can be related to conductor size by the formula:A = Minimum required cross section area in mm2
t = Operating time of disconnecting device in seconds
Isc = RMS Short Circuit current Value in Ampere
C = Constant equal to 0.0297 for copper & 0.0125 for aluminum
T2 = Final temp. ° C (max. short circuit temperature)
T1 = Initial temp. ° C (max. cable operating temperature – normal conditions)
T0 = 234.5° C for copper and 228.1° C for aluminum
Equation-1 can be simplified to obtain the expression for minimum conductor size as given below in equation-2:
Now K can be defined as a Constant whose value depends upon the conductor material, its insulation and boundary conditions of initial and final temperature because during short circuit conditions, the temperature of the conductor rises rapidly. The short circuit capacity is limited by the maximum temperature capability of the insulation. The value of K hence is as given in Table 2.
Boundary conditions of initial and final temperature for different insulation is as given under in Table 1 below.
Table 1
Insulation material | Final temperature T2 | Initial temperature T1 |
PVC | 160° C | 70° C |
Butyl Rubber | 220° C | 85° C |
XLPE / EPR | 250° C | 90° C |
Table 2
Material → | Copper | Aluminum | ||||
Insulation → | PVC | Butyl Rubber | XLPE / EPR | PVC | Butyl Rubber | XLPE / EPR |
(K) 1 Second Current Rating in Amp/mm2 | 115 | 134 | 143 | 76 | 89 | 94 |
(K) 3 Second Current Rating in Amp/mm2 | 66 | 77 | 83 | 44 | 51 | 54 |
In the final equation-2 we have determined the value of constant K. Now the value of t is to be determined. The fault current (ISC) in the above equation varies with time. However, calculating the exact value of the fault current and sizing the power cable based on that can be complicated. To simplify the process the cable can be sized based on the interrupting capability of the circuit breakers/fuses that protect them.
This approach assumes that the available fault current is the maximum capability of the breaker/fuse and also accounts for the cable impedances in reducing the fault levels.
Click here to access the full article
No comments:
Post a Comment