Tuesday, October 14, 2014

Shielding of Power Cables




Medium and high-voltage power cables, in circuits over 2000 volts, usually have a shield layer of copper or aluminum tape or conducting polymer. If an unshielded insulated cable is in contact with earth or a grounded object, the electrostatic field around the conductor will be concentrated at the contact point, resulting in corona discharge, and eventual destruction of the insulation.


As well, leakage current and capacitive current through the insulation presents a danger of electrical shock. The grounded shield equalizes electrical stress around the conductor, diverts any leakage current to ground. Be sure to apply stress relief/ cones at the shield ends, especially for cables operating at more than 2Kv to earth.

Paper Insulated CableShields on power cables are connected to earth ground at each shield end and at splices for redundancy to prevent shock even though induced current will flow in the shield. This current will produce losses and heating and will reduce the maximum current rating of the circuit. Tests show that having a bare grounding conductor adjacent to the insulated wires will conduct the fault current to earth quicker. On high current circuits the shields might be connected only at one end.
On very long high-voltage circuits, the shield may be broken into several sections since a long shield run may rise to dangerous voltages during a circuit fault. However, the shock hazard of having only one end of the shield grounded must be evaluated for the risk!
Shielding of an electric power cable is accomplished by surrounding the assembly or insulation with a grounded, conducting medium. This confines the dielectric field to the inside of this shield.




Shielding of power cables
Two distinct types of shields are used:
  • Metallic
  • Nonmetallic

The purposes of the insulation shield are to:
  • Obtain symmetrical radial stress distribution with the insulation.
  • Eliminate tangential and longitudinal stresses on the surface of the insulation.
  • Exclude from the dielectric field those materials such as braids, tapes, and fillers that are not intended as insulation.
  • Protect the cables from induced or direct aver-voltages. Shields do this by making the surge impedance uniform along the length of the cable and by helping to attenuate surge potentials.

Conductor Shielding

In cables rated over 2,000 volts, a conductor shield is required by industry standards. The purpose of the semiconducting, also called screening, material over the conductor is to provide a smooth cylinder rather than the relatively rough surface of a stranded conductor in order to reduce the stress concentration at the interface with the insulation. Conductor shielding has been used for cables with both laminar and extruded insulations.
The materials used are either semiconducting materials or ones that have a high dielectric constant and are known as stress control materials. Both serve the same function of stress reduction.
Conductor shields for paper insulated cables are either carbon black tapes or metallized paper tapes. The conductor shielding materials were originally made of semiconducting tapes that were helically wrapped over the conductor. Present standards still permit such a tape over the conductor. This is done, especially on large conductors, in order to hold the strands together firmly during the application of the extruded semiconducting material that is now required for medium voltage cables.
Experience with cables that only had a semi conducting tape was not satisfactory, so the industry changed their requirements to call for an extruded layer over the conductor.
In extruded cables, this layer is now extruded directly over the conductor and is bonded to the insulation layer that is applied over this stress relief layer. It is extremely important that there be no voids or extraneous material between those two layers.


Presentday extruded layers are not only clean (free from undesirable impurities) but are very smooth and round. This has greatly reduced the formation of water tress that could originate from irregular surfaces. By extruding the two layers at the same time, the conductor shield and the insulation are cured at the same time. This provides the inseparable bond that minimizes the chances of the formation of a void at the critical interface. For compatibility reasons, the extruded shielding layer is usually made from the same or a similar polymer as the insulation. Special carbon black is used to make the layer over the conductor semiconducting to provide the necessary conductivity. Industry standards require that the conductor semiconducting material have a maximum resistivity of 1,000 meter-ohms. Those standards also require that this material pass a long-time stability test for resistivity at the emergency operating temperature level to insure that the layer remains conductive and hence provides a long cable life.

A water-impervious material can be incorporated as part of the conductor shield to prevent radial moisture transmission. This layer consists of a thin layer of aluminum or lead sandwiched between semiconducting material. A similar laminate may be used for an insulation shield for the same reason.
There is no definitive standard that describes the class of extrudable shielding materials known as “super smooth, super clean”. It is not usually practical to use a manufacturer’strade name or product number to describeany material. The term “super smooth, super clean” is the only way at this writing to describe a class of material that provides a higher quality cable thanan earlier version. This is only an academic issue since the older type of materials are no longer used for medium voltage cable construction by known suppliers. The point is that these newer materials have tremendously improved cable performance in laboratory evaluations.

Insulation Shielding For Medium-Voltage Cables

The insulation shield for a medium voltage cable is made up of two components:
  • Semiconducting or stress relief layer
  • Metallic layer of tape or tap , drain wires, concentric neutral wires, or a metal tube.
They must function as a unit for a cable to achieve a long service life

Stress Relief Layer

The polymer layer used with exbuded cables has replaced the tapes shields that were used many years ago. This extruded layer is called the extruded insulation shield or screen. Its properties and compatibility requirements are similar to the conductor shield previously described except that standards require that the volume resistivity of this external layer be limited to 500 meter-ohms.
The nonmetallic layer is directly over the insulation and the voltage stress at that interface is lower than at the conductor shield interface.. This outer layer is not required to be bonded for cables rated up to 35 kV. At voltages above that, it is strongly recommended that this layer be bonded to the insulation .
Since most users want this layer to be easily removable, the Association of Edison Illuminating Companies (AEIC) has established strip tension limits. Presently these limits are that a 1/2 inch wide strip cut parallel to the conductor peel off with a minimum of 6 pounds and a minimum of 24 pounds of force that is at a 90º angle to the insulation surface.

Metallic Shield

The metallic portion of the insulation shield or screen is necessary to provide a low resistance path for charging current to flow to ground. It is important to realize that the extruded shield materials will not survive a sustained current flow of more than a few milliamperes. These materials are capable of handing the small amounts of charging current, but cannot tolerate unbalanced or fault currents.
The metallic component of the insulation shield system must be able to accommodate these higher currents. On the other hand, an excessive amount of metal in the shield of a single-conductor cable is costly in two ways. First, additional metal over the amount that is actually required increases the initial cost of the cable. Secondly, the greater the metal component of the insulation shield, the higher the shield losses that result h m the flow of current in the central conductor.
A sufficient amount of metal must be provided in the cable design to ensure that the cable will activate the back-up protection in the event of any cable fault over the life of that cable. There is also the concern for shield losses.
It therefore becomes essential that:
  • The type of circuit interrupting equipment to be analyzed.What is the design and operational setting of the hse, recloser, or circuit breaker?
  • What fault current will the cable encounter over its life?
  • What shield losses can be tolerated? How many times is the shield to be grounded? Will there be shield breaks to prevent circulating currents?

Concentric Neutral Cables

When concentric neutral cables are specified, the concentric neutrals must be manufactured in accordance with ICEA standards. These wires must meet ASTM B3 for uncoated wires or B33 for coated wires.
These wires are applied directly over the nonmetallic insulation shield with a lay of not less than six or more than ten times the diameter over the concentric wires.

Shielding Of Low Voltage Cables

Shielding of low voltage cablesShielding of low voltage cables is generally required where inductive interference can be a problem. In numerous communication, instrumentation, and control cable applications, small electrical signals may be transmitted on the cable conductor and amplified at the receiving end. Unwanted signals (noise) due to inductive interference can beaslargeasthedesiredsignal. This can result in false signals or audible noise that can effect voice communications.
Across the entire frequency spectrum, it is necessary to separate disturbances into electric field effects and magnetic field effects.

Electric Fields

Electric field effects are those which are a function of the capacitive coupling or mutual capacitance between the circuits. Shielding can be effected by a continuous metal shield to isolate the disturbed circuit fiom the disturbing circuit.
Even semiconducting extrusions or tapes supplemented by a grounded dmin wire can serve some shielding function for electric field effects.

Magnetic Fields

Magnetic field effects are the result of a magnetic field coupling between circuits. This is a bit more complex thanfor electrical effects.
At relatively low frequencies, the energy emitted from the source is treated as radiation. This increases with the square of the frequency. This electromagnetic radiation can cause dislxrbancesat considerable distance and will penetrate any “openings” in the shielding. This can occur with braid shields or tapes that are not overlapped. The type of metal used in the shield also can effect the amount of disturbance.
Any metallic shield material, as opposed to magnetic metals, will provide some shield due to the eddy currents that are set up in the metallic shield by the impinging field. These eddy currents tend to neutralize the disturbing field. Non-metallic, semiconducting shielding is not effective for magnetic effects. In general, the most effective shielding is a complete steel conduit, but thisis not always practical.

The effectiveness of a shield is called the “shielding factor” and is given as:

SF = Induced voltage in shield circuit / Inducted voltage in unshielded circuit

Test circuits to measure the effectiveness of various shielding designs against electrical field effects and magnetic field effects have been reported by Gooding and Slade.


http://electrical-engineering-portal.com/shielding-of-power-cables

Practices for Grounding and Bonding of Cable Trays

Grounding and bonding of cable trays
Grounding and bonding of cable trays (on photo: Ground wire connected to cable tray; photo credit: solarprofessional.com)

Metallic Cable Trays

Cable tray may be used as the Equipment Grounding Conductor (EGC) in any installation where qualified persons will service the installed cable tray system. There is no restriction as to where the cable tray system is installed. The metal in cable trays may be used as the EGC as per the limitations of table 392.60(A).
All metallic cable trays shall be grounded as required in Article 250.96 regardless of whether or not the cable tray is being used as an equipment grounding conductor (EGC).
The EGC is the most important conductor in an electrical system as its function is electrical safety.
Grounding and bonding of cable trays
Grounding and bonding of cable trays
There are three wiring options for providing an EGC in a cable tray wiring system:
  1. An EGC conductor in or on the cable tray.
  2. Each multi-conductor cable with its individual EGC conductor.
  3. The cable tray itself is used as the EGC in qualifying facilities.

Correct Bonding Practices To Assure That The Cable Tray System Is Properly Grounded

If an EGC cable is installed in or on a cable tray, it should be bonded to each or alternate cable tray sections via grounding clamps (this is not required by the NEC® but it is a desirable practice). In addition to providing an electrical connection between the cable tray sections and the EGC, the grounding clamp mechanically anchors the EGC to the cable tray so that under fault current conditions the magnetic forces do not throw the EGC out of the cable tray.
A bare copper equipment grounding conductor should not be placed in an aluminum cable tray due to the potential for electrolytic corrosion of the aluminum cable tray in a moist environment. For such installations, it is best to use an insulated conductor and to remove the insulation where bonding connections are made to the cable tray, raceways, equipment enclosures, etc. with tin or zinc plated connectors.

NEC Table 250.122 - Minimum size equipment grounding conductors for grounding raceway and equipment
Minimum size equipment grounding conductors for grounding raceway and equipment
Table 2 – Minimum size equipment grounding conductors for grounding raceway and equipment

Aluminum Cable Tray Systems

Table 392.60(A) – Metal area requirements for cable trays used as equipment grounding conductors
Metal area requirements for cable trays
Metal area requirements for cable trays used as equipment grounding conductors

For Sl units: 1 square inch = 645
* Total cross-sectional area of both side rails for ladder or trough cable trays or the minimum cross-sectional area of metal in channel cable trays or cable trays of one-piece construction.
** Steel cable trays shall not be used as equipment grounding conductors for circuits with ground-fault protection above 600 amperes. Aluminum cable trays shall not be used as equipment grounding conductors for circuits with ground-fault protection above 2000 amperes.

Table 392.60(A) “Metal Area Requirements for Cable Trays used as Equipment Grounding Conductors” shows the minimum cross-sectional area of cable tray side rails (total of both side rails) required for the cable tray to be used as the Equipment Grounding Conductor (EGC) for a specific Fuse Rating, Circuit Breaker Ampere Trip Rating or Circuit Breaker Ground Fault Protective Relay Trip Setting.
These are the actual trip settings for the circuit breakers and not the maximum permissible trip settings which in many cases are the same as the circuit breaker frame size.
If the maximum ampere rating of the cable tray is not sufficient for the protective device to be used, the cable tray cannot be used as the EGC and a separate EGC must be included within each cable assembly or a separate EGC has to be installed in or attached to the cable tray.
For specific areas requiring bonding for electrical continuity, refer to Figures 1-4.
Expansion splice plates and horizontal adjustable plates
Figure 1 left: Expansion splice plates; Figure 2 right: Horizontal adjustable plates

Figure 3 left: Discontinuos segments; Figure 4 right: Cable tray sections vertical adjustable splice plate
Figure 3 left: Discontinuos segments; Figure 4 right: Cable tray sections vertical adjustable splice plate

Non-metallic cable trays do not serve as a conductor. It is also recommended that wire mesh cable trays not be used as an equipment grounding conductor.
Although permitted by the NEC, it is recommended due to the unique nature of the wire mesh, fittings are manufactured in the field from straight sections by cutting away the current carrying structural wires, reducing the current-carrying capability of the system. As such, the use of wire mesh cable trays as an equipment grounding conductor is not recommended.
If the wire mesh cable tray is to be used as an equipment grounding conductor, then the installation of a ground wire is recommended.
If a wire mesh cable tray is supporting cable with a built-in equipment grounding conductor or control or signal cables, then the tray should have a low impedance path to a non-system ground to reduce noise and remove induced or stray currents. A separate grounding cable attached to the wire mesh cable tray is not usually required.

http://electrical-engineering-portal.com/practices-for-grounding-and-bonding-of-cable-trays

Thursday, October 2, 2014

4 ways in which noise can enter a signal cable and its control - PART 2

Continued from part 1… Read here.

Electromagnetic induction and RFI

In previous part of this technical article, I wrote about electrical noise occurs or is transmitted into a signal cable system in the following four ways:
  1. Galvanic (direct electrical contact) – part 1
  2. Electrostatic coupling – part 1
  3. Electromagnetic induction
  4. Radio frequency interference (RFI)

3. Magnetic or inductive coupling

This depends on the rate of change of the noise current and the mutual inductance between the noise system and the signal wires.
Expressed slightly differently, the degree of noise induced by magnetic coupling will depend on the:
  • Magnitude of the noise current
  • Frequency of the noise current
  • Area enclosed by the signal wires (through which the noise current magnetic flux cuts)
  • Inverse of the distance from the disturbing noise source to the signal wires.
The effect of magnetic coupling is shown in Figure 1 below.
Magnetic coupling
Figure 1 – Magnetic coupling

The easiest way of reducing the noise voltage caused by magnetic coupling is to twist the signal conductors. This results in lower noise due to the smaller area for each loop.
This means less magnetic flux to cut through the loop and consequently a lower induced noise voltage. In addition, the noise voltage that is induced in each loop tends to cancel out the noise voltages from the next sequential loop.
Hence an even number of loops will tend to have the noise voltages canceling each other out. It is assumed that the noise voltage is induced in equal magnitudes in each signal wire due to the twisting of the wires giving a similar separation distance from the noise voltage (see Figure 3).
Twisting of wires to reduce magnetic coupling
Figure 3 – Twisting of wires to reduce magnetic coupling

The second approach is to use a magnetic shield around the signal wires (refer Figure 4).
The magnetic flux generated from the noise currents induces small eddy currents in the magnetic shield. These eddy currents then create an opposing magnetic flux Φ1 to the original flux Φ2. This means a lesser flux (Φ2 − Φ1) reaches our circuit!
Use of magnetic shield to reduce magnetic coupling
Figure 4 – Use of magnetic shield to reduce magnetic coupling

Note: The magnetic shield does not require earthing. It works merely by being present. High-permeability steel makes best magnetic shields for special applications. However, galvanized steel conduit makes a quite effective shield.


http://electrical-engineering-portal.com/4-ways-in-which-noise-can-enter-a-signal-cable-and-its-control-part-2

4 ways in which noise can enter a signal cable and its control - PART 1

Few words about interference…

Noise, or interference, can be defined as undesirable electrical signals, which distort or interfere with an original (or desired) signal. Noise could be transient (temporary) or constant.

Unpredictable transient noise is caused, for example, by lightning.

Constant noise can be due to the predictable 50 or 60 Hz AC ‘hum’ from power circuits or harmonic multiples of power frequency close to the data communications cable. This unpredictability makes the design of a data communications system quite challenging.
Electrical noise occurs or is transmitted into a signal cable system in the following four ways:
  1. Galvanic (direct electrical contact)
  2. Electrostatic coupling
  3. Electromagnetic induction (in part 2)
  4. Radio frequency interference (RFI) (in part 2)
If two signal channels within a single data cable share the same signal reference conductor (common return path), the voltage drop caused by one channel’s signal in the reference conductor can appear as a noise in the other channel and will result in interference. This is called galvanic noise.
Electrostatic noise is one, which is transmitted through various capacitances present in the system such as between wires within a cable, between power and signal cables, between wires to ground or between two windings of a transformer. These capacitances present low-impedance paths when noise voltages of high frequency are present.


Thus noise can jump across apparently non- conducting paths and create a disturbance in signal/data circuits.
Electromagnetic interference (EMI) is caused when the flux lines of a strong magnetic field produced by a power conductor cut other nearby conductors and cause induced voltages to appear across them.

When signal cables are involved in the EMI process, this causes a noise in signal circuits. This is aggravated when harmonic currents are present in the system. Higher order harmonics have much higher frequencies than the normal AC wave and result in interference particularly in communication circuits.


Radio frequency interference involves coupling of noise through radio frequency interference. We will now describe these in some detail.



http://electrical-engineering-portal.com/4-ways-in-which-noise-can-enter-a-signal-cable-and-its-control-part-1

Tuesday, September 16, 2014

Hygienic Cable Connections Made Easy



Whats the most important thing to bear in mind when designing systems for hygienic manufacturing environments? Smooth, stainless steel surfaces might be one answer. But more fundamentally, hygiene requires attention to detail.

Take cable glands, for example.  Standard models, while suitable for most industrial settings, typically have exposed threads, tiny openings and protruding surface features that make them less than ideal from a hygiene standpoint.  Recently, our engineers have turned their attention to these easy-to-overlook cable gland details. The result is a new hygienic cable connector called SKINTOP® INOX.

Made from food-grade 316L stainless steel,  SKINTOP® INOX features enclosed, sealed threads. And its exterior surfaces have no gaps or protruding features that can trap particulate or microbes. Even the number of tooling flats, which blend seamlessly with the surrounding housing surfaces, have been reduced to just two. SKINTOP® INOX cable glands finally feature integral food-grade silicone o-rings for IP 68 protection at 5 bar.

Aside from their outward appearance and internal seals, the new hygienic glands meet the same high performance and ease-of-use standards as our other SKINTOP® products. These include:

*  Operating temperature range of -30° to 100° C.
*  Wide clamping range of 7 to 13 mm with M20 x 1.5 threads.
* Compliance with ISO 14159 standards for machinery hygiene.


The first SKINTOP® INOX models, which were introduced last month, are intended for use in splash zones and not for direct contact with food or pharmaceuticals. Models for use in washdown and direct contact applications will be introduced soon.

Download the technical specifications for SKINTOP® INOX here.


http://www.lappusa.com/PDF/Page526_SKINTOP_INOX_INOX-R.pdf




Tuesday, September 9, 2014

Challenges of high-acceleration servo motors

As machine tools get faster and faster, there’s a growing need for high-acceleration servo systems. These servo systems obviously require more robust motors and mechanical components. 

What’s less obvious is that they also need power and signal cables that have been designed to withstand acceleration-related stresses.
 
Lapp's brand new new lineup of high-acceleration servo cables, includes ÖLFLEX® SERVO FD 796 CP.  

 
This high-acceleration cable’s features include extra-fine Class 6 copper stranding, polypropylene insulation, non-woven wrapping, tinned copper braiding and a polyurethane jacketing. The cable optionally contains either one or two control pairs.

The new cable supports accelerations in excess of 5g and travel speeds up to 5 m/sec. Travel distances can range up to 100 m. Intended for flexible applications, it has a minimum bend radius of 7.5 x OD.
 
Other than its outstanding ability to withstand high accelerations, FD 796 CP behaves much like any other high-performance servo cable. It resists oil and flame to UL standards. Temperature range for flexible applications is –40 to 80ºC.


If you’d like to learn more the cable design challenges that result from high accelerations, download our latest white paper.

http://landing.lappusa.com/acceleration

Wednesday, September 3, 2014

New Servo Cables Withstand High Accelerations

As machine tools get faster and faster, there’s a growing need for high-acceleration servo systems. These servo systems obviously require more robust motors and mechanical components. What’s less obvious is that they also need power and signal cables that have been designed to withstand acceleration-related stresses.


At the IMTS Show next month (Booth E–4624), we’ll have Lapp technical experts on hand to discuss the effects of high acceleration motion on cable lifecycle and performance. We’ll also be showcasing our brand new lineup of high-acceleration servo cables, including ÖLFLEX® SERVO FD 796 CP.

This high-acceleration cable’s features include extra-fine Class 6 copper stranding, polypropylene insulation, non-woven wrapping, tinned copper braiding and a polyurethane jacketing. The cable optionally contains either one or two control pairs.


The new cable supports accelerations in excess of 5g and travel speeds up to 5 m/sec. Travel distances can range up to 100 m. Intended for flexible applications, it has a minimum bend radius of 7.5 x OD.

Other than its outstanding ability to withstand high accelerations, FD 796 CP behaves much like any other high-performance servo cable. It resists oil and flame to UL standards. Temperature range for flexible applications is –40 to 80ºC.


Download out latest whitepaper if you’d like to learn more the cable design challenges that result from high accelerations


http://content.lappgroup.com/fileadmin/DAM/Lapp_USA/Whitepapers/High_Acceleration_WP.pdf