Separation distances
In situations where there are a large number of cables varying in voltage and current levels, the
IEEE 518-1982 standard has developed a useful set of tables indicating separation distances for the various classes of cables.
There are
four classification levels of susceptibility for cables.
Susceptibility, in this context, is understood to be an indication of how well the signal circuit can differentiate between the
undesirable noise and required signal. It follows that a data communication physical standard such as
RS-232E would have a high susceptibility, and a 1000-V, 200-A AC cable has a low susceptibility.
IEEE 518 – 1982 standard
The four susceptibility levels defined by the IEEE 518 – 1982 standard are briefly:
Level 1 (High)
– This is defined as analog signals less than 50 V and digital signals
less than 15 V. This would include digital logic buses and telephone
circuits. Data communication cables fall into this category.
Level 2 (Medium) – This category includes analog signals greater than 50 V and switching circuits.
Level 3 (Low)
– This includes switching signals greater than 50 V and analog signals
greater than 50 V. Currents less than 20 A are also included in this
category.
Level 4 (Power) – This includes voltages in the range 0–1000 V and currents in the range 20–800 A. This applies to both AC and DC circuits.
The IEEE 518 also provides for three different situations
when calculating the separation distance
required between the various levels of susceptibilities. In considering
the specific case where one cable is a high-susceptibility cable and
the other cable has a varying susceptibility, the required separation
distance would vary as follows:
Both cables contained in a separate tray:
- Level 1 to level 2-30 mm
- Level 1 to level 3-160 mm
- Level 1 to level 4-670 mm
One cable contained in a tray and the other in conduit:
- Level 1 to level 2-30 mm
- Level 1 to level 3-110 mm
- Level 1 to level 4-460 mm
Both cables contained in separate conduit:
- Level 1 to level 2-30 mm
- Level 1 to level 3-80 mm
- Level 1 to level 4-310 mm.
The figures are approximate as the original standard is quoted in inches.
Trays and conduits
A few words need to be said about
the construction of the trays and conduits. It
is expected that the trays are manufactured from metal and be firmly
earthed with complete continuity throughout the length of the tray. The
trays should also be fully covered preventing the possibility of any
area being without shielding.
Briefly galvanic noise
can easily be avoided by refraining from the use of a shared signal
reference conductor, in other words, keeping the two signal channels
galvanically separate so that no interference takes place.
Electromagnetic induction
can be minimized in several ways. One way is to put the source of
electromagnetic flux within a metallic enclosure, a magnetic screen.
Such a screen restricts the flow of magnetic flux from going beyond its
periphery so that it cannot interfere with external conductors. A
similar screen around the receptor of EMI can mitigate noise by not
allowing flux lines inside its enclosure but to take a path along the
plane of its surface.
Physical separation between the noise source and the receptor will also reduce magnetic coupling and therefore the interference.