Cable Glands For Full EMI Protection



Winning the war against electromagnetic interference (EMI) on today’s factory floors requires attention to detail. One of those details involves the ability of cable glands to contribute to a reliable grounding system.
Left unprotected, cable glands transmit electrical noise that can wreak havoc on motor-driven industrial processes. Many types of cable glands feature shielding to keep EMI at bay, yet the effectiveness of that shielding  can vary widely from product to product.
The ease of installation can vary as well. Some shielding options have difficult termination methods or grounding connections that can drive up labor cost and time.  
With SKINTOP® MS-M Brush, our engineers have addressed both the shielding and installation issues. As its name suggests, this cable gland features a brush-type grounding connection that:
•  Enhances EMI control. Unlike other connection methods, such as the grounding clamps commonly used on drive systems, the brush provides continuous 360° contact around the cable’s screen braid. This continuous contact protects against EMI by lowering the resistance of current ground path and providing a low impedance connection between the cable shield and the housing.
•  Eases Installation. Making an EMI-free connection between cable and the SKINTOP cable gland is simple. Installers simply insert the cable, push the screen braid into the brush and tighten the cable gland assembly. Other grounding methods require far more effort to make the termination. Earth sleeves, for example, can serve as an effective grounding method, but their termination process requires precision measurements and exacting preparation of the stripped area.
In addition to its innovative brush-type connection, SKINTOP® MS-M Brush offers IP 68 protection and resists temperatures up to 100ºC. Until recently, it was available only in metric sizes, ranging from M–25X1.5 to M–110X2.0. This month, we’ve introduced NPT sizes from ¾” to 2”.
Click here for detailed technical information on SKINTOP® MS-M Brush

Thursday, October 2, 2014

4 ways in which noise can enter a signal cable and its control - PART 2

Continued from part 1… Read here.

Electromagnetic induction and RFI

In previous part of this technical article, I wrote about electrical noise occurs or is transmitted into a signal cable system in the following four ways:
  1. Galvanic (direct electrical contact) – part 1
  2. Electrostatic coupling – part 1
  3. Electromagnetic induction
  4. Radio frequency interference (RFI)

3. Magnetic or inductive coupling

This depends on the rate of change of the noise current and the mutual inductance between the noise system and the signal wires.
Expressed slightly differently, the degree of noise induced by magnetic coupling will depend on the:
  • Magnitude of the noise current
  • Frequency of the noise current
  • Area enclosed by the signal wires (through which the noise current magnetic flux cuts)
  • Inverse of the distance from the disturbing noise source to the signal wires.
The effect of magnetic coupling is shown in Figure 1 below.
Magnetic coupling
Figure 1 – Magnetic coupling

The easiest way of reducing the noise voltage caused by magnetic coupling is to twist the signal conductors. This results in lower noise due to the smaller area for each loop.
This means less magnetic flux to cut through the loop and consequently a lower induced noise voltage. In addition, the noise voltage that is induced in each loop tends to cancel out the noise voltages from the next sequential loop.
Hence an even number of loops will tend to have the noise voltages canceling each other out. It is assumed that the noise voltage is induced in equal magnitudes in each signal wire due to the twisting of the wires giving a similar separation distance from the noise voltage (see Figure 3).
Twisting of wires to reduce magnetic coupling
Figure 3 – Twisting of wires to reduce magnetic coupling

The second approach is to use a magnetic shield around the signal wires (refer Figure 4).
The magnetic flux generated from the noise currents induces small eddy currents in the magnetic shield. These eddy currents then create an opposing magnetic flux Φ1 to the original flux Φ2. This means a lesser flux (Φ2 − Φ1) reaches our circuit!
Use of magnetic shield to reduce magnetic coupling
Figure 4 – Use of magnetic shield to reduce magnetic coupling

Note: The magnetic shield does not require earthing. It works merely by being present. High-permeability steel makes best magnetic shields for special applications. However, galvanized steel conduit makes a quite effective shield.


http://electrical-engineering-portal.com/4-ways-in-which-noise-can-enter-a-signal-cable-and-its-control-part-2

4 ways in which noise can enter a signal cable and its control - PART 1

Few words about interference…

Noise, or interference, can be defined as undesirable electrical signals, which distort or interfere with an original (or desired) signal. Noise could be transient (temporary) or constant.

Unpredictable transient noise is caused, for example, by lightning.

Constant noise can be due to the predictable 50 or 60 Hz AC ‘hum’ from power circuits or harmonic multiples of power frequency close to the data communications cable. This unpredictability makes the design of a data communications system quite challenging.
Electrical noise occurs or is transmitted into a signal cable system in the following four ways:
  1. Galvanic (direct electrical contact)
  2. Electrostatic coupling
  3. Electromagnetic induction (in part 2)
  4. Radio frequency interference (RFI) (in part 2)
If two signal channels within a single data cable share the same signal reference conductor (common return path), the voltage drop caused by one channel’s signal in the reference conductor can appear as a noise in the other channel and will result in interference. This is called galvanic noise.
Electrostatic noise is one, which is transmitted through various capacitances present in the system such as between wires within a cable, between power and signal cables, between wires to ground or between two windings of a transformer. These capacitances present low-impedance paths when noise voltages of high frequency are present.


Thus noise can jump across apparently non- conducting paths and create a disturbance in signal/data circuits.
Electromagnetic interference (EMI) is caused when the flux lines of a strong magnetic field produced by a power conductor cut other nearby conductors and cause induced voltages to appear across them.

When signal cables are involved in the EMI process, this causes a noise in signal circuits. This is aggravated when harmonic currents are present in the system. Higher order harmonics have much higher frequencies than the normal AC wave and result in interference particularly in communication circuits.


Radio frequency interference involves coupling of noise through radio frequency interference. We will now describe these in some detail.



http://electrical-engineering-portal.com/4-ways-in-which-noise-can-enter-a-signal-cable-and-its-control-part-1