Showing posts with label tray cable. Show all posts
Showing posts with label tray cable. Show all posts

Wednesday, September 28, 2016

Practices for grounding and bonding of cable trays

Metallic Cable Trays

Cable tray may be used as the Equipment Grounding Conductor (EGC) in any installation where qualified persons will service the installed cable tray system. There is no restriction as to where the cable tray system is installed. The metal in cable trays may be used as the EGC as per the limitations of table 392.60(A).
All metallic cable trays shall be grounded as required in Article 250.96 regardless of whether or not the cable tray is being used as an equipment grounding conductor (EGC).
The EGC is the most important conductor in an electrical system as its function is electrical safety.

Grounding and bonding of cable trays
 
 

There are three wiring options for providing an EGC in a cable tray wiring system:
  1. An EGC conductor in or on the cable tray.
  2. Each multi-conductor cable with its individual EGC conductor.
  3. The cable tray itself is used as the EGC in qualifying facilities.

Correct bonding practices

To assure that the cable tray system is properly grounded

If an EGC cable is installed in or on a cable tray, it should be bonded to each or alternate cable tray sections via grounding clamps (this is not required by the NEC® but it is a desirable practice)
In addition to providing an electrical connection between the cable tray sections and the EGC, the grounding clamp mechanically anchors the EGC to the cable tray so that under fault current conditions the magnetic forces do not throw the EGC out of the cable tray.
A bare copper equipment grounding conductor should not be placed in an aluminum cable tray due to the potential for electrolytic corrosion of the aluminum cable tray in a moist environment.
For such installations, it is best to use an insulated conductor and to remove the insulation where bonding connections are made to the cable tray, raceways, equipment enclosures, etc. with tin or zinc plated connectors.

Click here to access the full article

Tuesday, November 3, 2015

New Industrial Ethernet Cables For Tray Applications



Industrial Ethernet offers plenty of flexibility when it comes to designing complex automation networks.  Until recently, you couldn't say the same about data cables used in these networks.

CAT 5e Ethernet cables have traditionally been intended for stationary applications. And in the early days of industrial Ethernet, that limitation didn't matter much. Modern automation systems, however, increasingly require a new breed of Industrial Ethernet cables that can withstand more flexible conditions.

Our new ETHERLINE® Tray cable has been designed with flexibility in mind.  With its PLTC rating, the ETHERLINE® Tray can be used in cable trays, interconnecting the Industrial Platform with the Commercial Infrastructure.  The new ETHERLINE cable features four twisted pairs of stranded copper, and can handle gigabit speeds. 

Reliable Data Transmission.  Reliable data transmission is a must-have if you want to control production equipment over an Ethernet network. Unfortunately the electrical noise that pervades most manufacturing environments makes error-free data transmission a challenge. The new ETHERLINE cables combat electrical noise with a rugged, flex-friendly foil and braid EMI shield.

The construction of the ETHERLINE TRAY CAT.5e consists of a polyolefin-based insulation and a PVC jacket. The cable has a 600V rating making it ideal for tray applications alongside power cables. When used in flexible applications, the cable can withstand operating temperature from -25 to 80ºC.  They have a characteristic impedance of 100 Ω, ±15 Ω, at 100 MHz. 

Important Approvals. The new ETHERLINE cables have a wide range of approvals, which lets them serve in many different settings. These approvals include:

  • CMR per UL 444
  • CMG per UL 444
  • PLTC per UL 13
  • AWM 2570 80°C 600V
  • c(UL) CMG
  • RoHS II


Click here , For more information on the ETHERLINE CAT.5e Tray Cable



Tuesday, October 20, 2015

New Industrial Ethernet Cables For Tray Applications



Industrial Ethernet offers plenty of flexibility when it comes to designing complex automation networks.  Until recently, you couldn't say the same about data cables used in these networks.

CAT 5e Ethernet cables have traditionally been intended for stationary applications. And in the early days of industrial Ethernet, that limitation didn't matter much. Modern automation systems, however, increasingly require a new breed of Industrial Ethernet cables that can withstand more flexible conditions.

Our new ETHERLINE® Tray cable has been designed with flexibility in mind.  With its PLTC rating, the ETHERLINE® Tray can be used in cable trays, interconnecting the Industrial Platform with the Commercial Infrastructure.  The new ETHERLINE cable features four twisted pairs of stranded copper, and can handle gigabit speeds. 

Reliable Data Transmission.  Reliable data transmission is a must-have if you want to control production equipment over an Ethernet network. Unfortunately the electrical noise that pervades most manufacturing environments makes error-free data transmission a challenge. The new ETHERLINE cables combat electrical noise with a rugged, flex-friendly foil and braid EMI shield.

The construction of the Etherline Tray CAT.5e consists of a polyolefin-based insulation and a PVC jacket. The cable has a 600V rating making it ideal for tray applications alongside power cables. When used in flexible applications, the cable can withstand operating temperature from -25 to 80ºC.  They have a characteristic impedance of 100 Ω, ±15 Ω, at 100 MHz. 

Important Approvals. The new ETHERLINE cables have a wide range of approvals, which lets them serve in many different settings. These approvals include:

  • CMR per UL 444
  • CMG per UL 444
  • PLTC per UL 13
  • AWM 2570 80°C 600V
  • c(UL) CMG
  • RoHS II


Click here for more information on the ETHERLINE CAT.5e Tray Cable

Tuesday, October 14, 2014

Practices for Grounding and Bonding of Cable Trays

Grounding and bonding of cable trays
Grounding and bonding of cable trays (on photo: Ground wire connected to cable tray; photo credit: solarprofessional.com)

Metallic Cable Trays

Cable tray may be used as the Equipment Grounding Conductor (EGC) in any installation where qualified persons will service the installed cable tray system. There is no restriction as to where the cable tray system is installed. The metal in cable trays may be used as the EGC as per the limitations of table 392.60(A).
All metallic cable trays shall be grounded as required in Article 250.96 regardless of whether or not the cable tray is being used as an equipment grounding conductor (EGC).
The EGC is the most important conductor in an electrical system as its function is electrical safety.
Grounding and bonding of cable trays
Grounding and bonding of cable trays
There are three wiring options for providing an EGC in a cable tray wiring system:
  1. An EGC conductor in or on the cable tray.
  2. Each multi-conductor cable with its individual EGC conductor.
  3. The cable tray itself is used as the EGC in qualifying facilities.

Correct Bonding Practices To Assure That The Cable Tray System Is Properly Grounded

If an EGC cable is installed in or on a cable tray, it should be bonded to each or alternate cable tray sections via grounding clamps (this is not required by the NEC® but it is a desirable practice). In addition to providing an electrical connection between the cable tray sections and the EGC, the grounding clamp mechanically anchors the EGC to the cable tray so that under fault current conditions the magnetic forces do not throw the EGC out of the cable tray.
A bare copper equipment grounding conductor should not be placed in an aluminum cable tray due to the potential for electrolytic corrosion of the aluminum cable tray in a moist environment. For such installations, it is best to use an insulated conductor and to remove the insulation where bonding connections are made to the cable tray, raceways, equipment enclosures, etc. with tin or zinc plated connectors.

NEC Table 250.122 - Minimum size equipment grounding conductors for grounding raceway and equipment
Minimum size equipment grounding conductors for grounding raceway and equipment
Table 2 – Minimum size equipment grounding conductors for grounding raceway and equipment

Aluminum Cable Tray Systems

Table 392.60(A) – Metal area requirements for cable trays used as equipment grounding conductors
Metal area requirements for cable trays
Metal area requirements for cable trays used as equipment grounding conductors

For Sl units: 1 square inch = 645
* Total cross-sectional area of both side rails for ladder or trough cable trays or the minimum cross-sectional area of metal in channel cable trays or cable trays of one-piece construction.
** Steel cable trays shall not be used as equipment grounding conductors for circuits with ground-fault protection above 600 amperes. Aluminum cable trays shall not be used as equipment grounding conductors for circuits with ground-fault protection above 2000 amperes.

Table 392.60(A) “Metal Area Requirements for Cable Trays used as Equipment Grounding Conductors” shows the minimum cross-sectional area of cable tray side rails (total of both side rails) required for the cable tray to be used as the Equipment Grounding Conductor (EGC) for a specific Fuse Rating, Circuit Breaker Ampere Trip Rating or Circuit Breaker Ground Fault Protective Relay Trip Setting.
These are the actual trip settings for the circuit breakers and not the maximum permissible trip settings which in many cases are the same as the circuit breaker frame size.
If the maximum ampere rating of the cable tray is not sufficient for the protective device to be used, the cable tray cannot be used as the EGC and a separate EGC must be included within each cable assembly or a separate EGC has to be installed in or attached to the cable tray.
For specific areas requiring bonding for electrical continuity, refer to Figures 1-4.
Expansion splice plates and horizontal adjustable plates
Figure 1 left: Expansion splice plates; Figure 2 right: Horizontal adjustable plates

Figure 3 left: Discontinuos segments; Figure 4 right: Cable tray sections vertical adjustable splice plate
Figure 3 left: Discontinuos segments; Figure 4 right: Cable tray sections vertical adjustable splice plate

Non-metallic cable trays do not serve as a conductor. It is also recommended that wire mesh cable trays not be used as an equipment grounding conductor.
Although permitted by the NEC, it is recommended due to the unique nature of the wire mesh, fittings are manufactured in the field from straight sections by cutting away the current carrying structural wires, reducing the current-carrying capability of the system. As such, the use of wire mesh cable trays as an equipment grounding conductor is not recommended.
If the wire mesh cable tray is to be used as an equipment grounding conductor, then the installation of a ground wire is recommended.
If a wire mesh cable tray is supporting cable with a built-in equipment grounding conductor or control or signal cables, then the tray should have a low impedance path to a non-system ground to reduce noise and remove induced or stray currents. A separate grounding cable attached to the wire mesh cable tray is not usually required.

http://electrical-engineering-portal.com/practices-for-grounding-and-bonding-of-cable-trays

Tuesday, June 25, 2013

New Lapp North America Catalog 2013

We are pleased to announce the 2013 Lapp USA Full Line Catalog is now available. Click here to get your complimentary printed copy today or view our digital edition below.

The new design and layout include:

  • More than 50 new products
  • A large number of innovative product and systems solutions
  • Structured directory by brand/product lines for quick look-up
  • Part number index for quick product look-up
  • Cross-reference to accessories and similar Lapp products
  • Quick-select charts to narrow down the search 

Click below to view the digital version





Call us today for all your wire & cable project needs.

Toll Free: 800-774-3539

Email: sales@lappusa.com
The Lapp Group

Tuesday, April 30, 2013

Video : Lapp Group Worldwide

The company was founded in 1957 by Oskar Lapp with ÖLFLEX® the first industrially produced signal cable in the world.

Today Lapp Cables produces cables and conductors for different industries and markets: mechanical and systems engineering, the automotive industry, MSR technology, electrical and installations engineering, EDC and more.

We currently supply 40,000 standard items from stock. We also develop and produce cables and conductors to customer specifications.

The Lapp Group has 17 production sites, 100 outlets and 41 sales organizations around the world. We employ 3,150 people.


Wednesday, March 20, 2013

VIDEO: ÖLFLEX® SERVO FD 796 CP

ÖLFLEX® SERVO FD 796 CP is an industrial grade servo cable with two options available: power only or power and feedback conductors. It has a polyurethane jacket and is designed for faster speed and acceleration which increases the economic efficiency of the machines.




Call 800-774-3539 or email us sales(at)lappusa.com for more information about this product or to order a sample.


High Performance Servo Cable for High Acceleration Motor & Drive Applications


NEW! ÖLFLEX® SERVO FD 796 CP

 

ÖLFLEX® SERVO FD 796 CP is an industrial grade servo cable with two options available: power only or power and feedback conductors. It has a polyurethane jacket and is designed for faster speed and acceleration which increases the economic efficiency of the machines.

Recommended Applications:
Motor connections for Servo motors, automation equipment, machine tool, food & beverage, automotive, packaging industry and is compatible with most major servo drive manufacturers.


Application Advantage:
  • Continuous flexing performance: acceleration up to 50m/s². travel speed up to 5m/s
  • Flexing distance up to 328 feet
  • Excellent cold temperature performance down to -40°C
  • The pairs are individually shielded for noise protection
  • PUR jacket for optimal oil and abrasion resistance
  • Halogen free

Construction:
Finely stranded bare copper conductors; core insultation is polypropylene; shielded pairs; overall tinned copper braid (85% coverage); non-woven material wrapping over the braid; specially formulated orange polyurethane outer jacket.

Access our full line catalog or if you have any questions, our team of experts will be glad to work with you in finding the best product for your application needs.



Call 800-774-3539 or email us sales(at)lappusa.com