Tuesday, October 20, 2015

New Industrial Ethernet Cables For Tray Applications



Industrial Ethernet offers plenty of flexibility when it comes to designing complex automation networks.  Until recently, you couldn't say the same about data cables used in these networks.

CAT 5e Ethernet cables have traditionally been intended for stationary applications. And in the early days of industrial Ethernet, that limitation didn't matter much. Modern automation systems, however, increasingly require a new breed of Industrial Ethernet cables that can withstand more flexible conditions.

Our new ETHERLINE® Tray cable has been designed with flexibility in mind.  With its PLTC rating, the ETHERLINE® Tray can be used in cable trays, interconnecting the Industrial Platform with the Commercial Infrastructure.  The new ETHERLINE cable features four twisted pairs of stranded copper, and can handle gigabit speeds. 

Reliable Data Transmission.  Reliable data transmission is a must-have if you want to control production equipment over an Ethernet network. Unfortunately the electrical noise that pervades most manufacturing environments makes error-free data transmission a challenge. The new ETHERLINE cables combat electrical noise with a rugged, flex-friendly foil and braid EMI shield.

The construction of the Etherline Tray CAT.5e consists of a polyolefin-based insulation and a PVC jacket. The cable has a 600V rating making it ideal for tray applications alongside power cables. When used in flexible applications, the cable can withstand operating temperature from -25 to 80ºC.  They have a characteristic impedance of 100 Ω, ±15 Ω, at 100 MHz. 

Important Approvals. The new ETHERLINE cables have a wide range of approvals, which lets them serve in many different settings. These approvals include:

  • CMR per UL 444
  • CMG per UL 444
  • PLTC per UL 13
  • AWM 2570 80°C 600V
  • c(UL) CMG
  • RoHS II


Click here for more information on the ETHERLINE CAT.5e Tray Cable

Monday, October 12, 2015

Differences in size and weight of equipment using copper and aluminium conductors

Common misconception

It is a common misconception that electrical equipment built using aluminum conductors will always be larger than the same equipment using copper conductors. While the actual conductor within the equipment will be larger with aluminum, many times the enclosure for the equipment is the same size whether copper or aluminum conductors are used.

This is true for switchboards, panelboards and most dry type transformers. Oil filled transformers will generally range from 2-5% larger when constructed with aluminum instead of copper windings.
The biggest size impact for electrical equipment when copper and aluminum conductors are considered is for busway. Since the actual conductor is the primary component within the busway, the size difference will be more apparent.
Busbar system inside low-voltage switchgear
Busbar system inside low-voltage switchgear (photo credit: Edvard Csanyi)

For example, GE busway is 4.5” thick, but the width will vary. For 1000A busway, the aluminum bus will be approximately 22% larger than copper bus and for 4000A busway, the size difference increases to almost 27% larger for the aluminum.
Even though the size for the aluminum bus is larger than for the copper bus, the weight difference is more dramatic and favors the aluminum bus.
Using the same examples used for size and assuming 3 phase, 4 wire busway, the 1000A copper is 50% heavier than the aluminum and for the 4000A busway, this value increases where copper is 73% heavier than the aluminum. This weight differential can be a huge factor for both the designer and the installer.

For example a 4000A, 10 foot section of copper bus is approximately 520 pounds, while the same busway with aluminum conductors is only 300 pounds. Installation by the contractor and mechanical support design by the engineer are considerations when the difference between the two products is considered.
 
The weight difference between equipment items with aluminum or copper conductors is present with all of the equipment types. For switchboards, the actual percentage will vary significantly with the amount of breakers installed in a section; and with a higher count of breakers, the percentage of weight contributed by the busbars diminishes.

However, if you just consider the weight of the steel enclosure and the busbars, copper bussed switchboard sections will be heavier than aluminum bussed switchboard sections, varying between 20% for 1000A sections to 29% for 4000A sections.

Click here for the full article

Friday, October 9, 2015

New Industrial Ethernet Cables For Tray Applications



Industrial Ethernet offers plenty of flexibility when it comes to designing complex automation networks.  Until recently, you couldn't say the same about data cables used in these networks.

CAT 5e Ethernet cables have traditionally been intended for stationary applications. And in the early days of industrial Ethernet, that limitation didn't matter much. Modern automation systems, however, increasingly require a new breed of Industrial Ethernet cables that can withstand more flexible conditions.

Our new ETHERLINE® Tray cable has been designed with flexibility in mind.  With its PLTC rating, the ETHERLINE® Tray can be used in cable trays, interconnecting the Industrial Platform with the Commercial Infrastructure.  The new ETHERLINE cable features four twisted pairs of stranded copper, and can handle gigabit speeds. 

Reliable Data Transmission.  Reliable data transmission is a must-have if you want to control production equipment over an Ethernet network. Unfortunately the electrical noise that pervades most manufacturing environments makes error-free data transmission a challenge. The new ETHERLINE cables combat electrical noise with a rugged, flex-friendly foil and braid EMI shield.

The construction of the Etherline Tray CAT.5e consists of a polyolefin-based insulation and a PVC jacket. The cable has a 600V rating making it ideal for tray applications alongside power cables. When used in flexible applications, the cable can withstand operating temperature from -25 to 80ºC.  They have a characteristic impedance of 100 Ω, ±15 Ω, at 100 MHz. 

Important Approvals. The new ETHERLINE cables have a wide range of approvals, which lets them serve in many different settings. These approvals include: 


  • CMR per UL 444
  • CMG per UL 444
  • PLTC per UL 13
  • AWM 2570 80°C 600V
  • c(UL) CMG
  • RoHS II


For more information on the ETHERLINE CAT.5e Tray Cable,  click here

Thursday, September 17, 2015

The Best Applications for Variable Frequency Drives (VFDs)

Advances

The most commonly used motor in building HVAC applications is the three-phase, induction motor, although some smaller applications may use a single-phase induction motor.
The Best Applications For Variable Frequency Drives (VFDs)VFDs can be applied to both.
While VFD controllers can be used with a range of applications, the ones that will produce the most significant benefits are those that require variable speed operation.
For example, the flow rate produced by pumps serving building HVAC systems can be matched to the building load by using a VFD to vary the flow rate.
Similarly, in systems that require a constant pressure be maintained regardless of the flow rate, such as in domestic hot and cold water systems, a VFD controlled by a pressure setpoint can maintain the pressure over most demand levels.

The majority of commercial and institutional HVAC systems use variable volume fan systems to distribute conditioned air. Most are controlled by a system of variable inlet vanes in the fan system and variable air volume boxes.
 
As the load on the system decreases, the variable air volume boxes close down, increasing the static pressure in the system. The fan’s controller senses this increase and closes down its inlet vanes. While using this type of control system will reduce system fan energy requirements, it is not as efficient or as accurate as a VFD-based system.

Another candidate for VFD use is a variable refrigerant flow systems. Variable refrigerant flow systems connect one or more compressors to a common refrigerant supply system that feeds multiple evaporators. By piping refrigerant instead of using air ducts, the distribution energy requirements are greatly reduced.
Because the load on the compressor is constantly changing based on the demand from the evaporators, a VFD can be used to control the operating speed of the compressor to match the load, reducing energy requirements under part-load conditions.

Additional VFD Applications

While the primary benefit of both of these VFD applications is energy savings, VFDs are well suited for use in other applications where energy conservation is of secondary importance. For example, VFDs can provide precise speed or torque control in some commercial applications.
Some specialized applications use dual fans or pumps. VFDs, with their precise speed control, can ensure that the two units are operated at the desired speed and do not end up fighting each other or having one unit carry more than its design load level.
Advances in technology have increased the number of loads that can be driven by the units. Today, units are available with voltage and current ratings that can match the majority of three-phase induction motors found in buildings. With 500 horsepower units or higher available, facility executives have installed them on large capacity centrifugal chillers where very large energy savings can be achieved.
One of the most significant changes that has taken place recently is that with the widespread acceptance of the units and the recognition of the energy and maintenance benefits, manufacturers are including VFD controls as part of their system in a number of applications. For example, manufacturers of centrifugal chillers offer VFD controls as an option on a number of their units.
Similarly, manufacturers of domestic water booster pump systems also offer the controls as part of their system, providing users with better control strategies while reducing energy and maintenance costs.

Click here to access the full article


Wednesday, September 16, 2015

Cable Spacing as a Means of Noise Mitigation

Separation distances

Cable spacing as a means of noise mitigation
In situations where there are a large number of cables varying in voltage and current levels, the IEEE 518-1982 standard has developed a useful set of tables indicating separation distances for the various classes of cables.
There are four classification levels of susceptibility for cables.
Susceptibility, in this context, is understood to be an indication of how well the signal circuit can differentiate between the undesirable noise and required signal. It follows that a data communication physical standard such as RS-232E would have a high susceptibility, and a 1000-V, 200-A AC cable has a low susceptibility.

IEEE 518 – 1982 standard

The four susceptibility levels defined by the IEEE 518 – 1982 standard are briefly:

Level 1 (High) – This is defined as analog signals less than 50 V and digital signals less than 15 V. This would include digital logic buses and telephone circuits. Data communication cables fall into this category.
Level 2 (Medium) – This category includes analog signals greater than 50 V and switching circuits.
Level 3 (Low) – This includes switching signals greater than 50 V and analog signals greater than 50 V. Currents less than 20 A are also included in this category.
Level 4 (Power) – This includes voltages in the range 0–1000 V and currents in the range 20–800 A. This applies to both AC and DC circuits.
The IEEE 518 also provides for three different situations when calculating the separation distance required between the various levels of susceptibilities. In considering the specific case where one cable is a high-susceptibility cable and the other cable has a varying susceptibility, the required separation distance would vary as follows:

Both cables contained in a separate tray:
  • Level 1 to level 2-30 mm
  • Level 1 to level 3-160 mm
  • Level 1 to level 4-670 mm
One cable contained in a tray and the other in conduit:
  • Level 1 to level 2-30 mm
  • Level 1 to level 3-110 mm
  • Level 1 to level 4-460 mm
Both cables contained in separate conduit:
  • Level 1 to level 2-30 mm
  • Level 1 to level 3-80 mm
  • Level 1 to level 4-310 mm.
The figures are approximate as the original standard is quoted in inches.

Trays and conduits


A few words need to be said about the construction of the trays and conduits. It is expected that the trays are manufactured from metal and be firmly earthed with complete continuity throughout the length of the tray. The trays should also be fully covered preventing the possibility of any area being without shielding.

Briefly galvanic noise can easily be avoided by refraining from the use of a shared signal reference conductor, in other words, keeping the two signal channels galvanically separate so that no interference takes place.
 
Electromagnetic induction can be minimized in several ways. One way is to put the source of electromagnetic flux within a metallic enclosure, a magnetic screen. Such a screen restricts the flow of magnetic flux from going beyond its periphery so that it cannot interfere with external conductors. A similar screen around the receptor of EMI can mitigate noise by not allowing flux lines inside its enclosure but to take a path along the plane of its surface.

Physical separation between the noise source and the receptor will also reduce magnetic coupling and therefore the interference.

 
Click here to access the full article

An example how to calculate voltage drop and size of electrical cable

Input information

Electrical details:

Electrical load of 80KW, distance between source and load is 200 meters, system voltage 415V three phase, power factor is 0.8, permissible voltage drop is  5%, demand factor is 1.

Cable laying detail:

An example how to calculate voltage drop and size of electrical cableCable is directed buried in ground in trench at the depth of 1 meter. Ground temperature is approximate 35 Deg. Number of cable per trench is 1. Number of run of cable is 1 run.

Soil details:

Thermal resistivity of soil is not known. Nature of soil is damp soil.



Ok, let’s dive into calculations…

  • Consumed Load = Total Load · Demand Factor:
    Consumed Load in KW = 80 · 1 = 80 KW
  • Consumed Load in KVA = KW/P.F.:
    Consumed Load in KVA = 80/0.8 = 100 KVA
  • Full Load Current = (KVA · 1000) / (1.732 · Voltage):
    Full Load Current = (100 · 1000) / (1.732 · 415) = 139 Amp.

Click here to access the full article

Tuesday, September 1, 2015

How to wire a HA 3/4 Rectangular Connector

HA Series connectors are used whenever space is limited. They provide the smallest possible footprint in a 10A power connector. Wiring a HA 3 series connector takes less than 10 min. Watch this video to learn how
 

Visit the Lapp Group website to access our comprehensive line of industrial connectors.